How to Read a Constant-Power Discharge Table for a UPS Lithium Battery

Every TC series datasheet carries a constant-power discharge table, and every row is a different battery: the same cabinet delivers far less power over a long runtime than over a short one. Read the row that matches the runtime you need.

A battery datasheet has one page that tells the truth about runtime: the constant-power discharge table. It lists the power one cabinet can deliver at fixed runtimes, and the numbers fall steeply as the runtime grows. Read it row by row, starting from the runtime the project needs.

Power Falls as Runtime Rises

Take the TC200D, a 512V 100Ah cabinet. Its table reads 228 kW at 10 minutes, 200 kW at 15 minutes, 100 kW at 30 minutes, 68 kW at 45 minutes and 51 kW at 60 minutes. Quadrupling the runtime from 15 to 60 minutes cuts the available power to about a quarter. The TC100E shows the same shape over a longer span: 98 kW at 30 minutes, 49 kW at 60 minutes, 24.5 kW at 120 minutes, 16.4 kW at 180 minutes and 9.8 kW at 300 minutes. Ten times the runtime, one tenth of the power.

The constant-current column tells the same story: the TC200D moves 490 A at 10 minutes and 100 A at 60 minutes, and the TC100E moves 200 A at 30 minutes and 20 A at 300 minutes.

Read the Row That Matches the Runtime

The headline power figure on a datasheet is usually the shortest row in the table, so it is the wrong row for most projects. The TC100 lists a maximum output of 114 kW, and that is its 10-minute value. At 30 minutes the same cabinet delivers 50.4 kW, and at 60 minutes 25.45 kW.

The TC100E makes the point from the other direction. Its maximum output is 98 kW, and that is its 30-minute value, because its table starts at 30 minutes. There is no 10-minute or 15-minute row for this cabinet, so the table cannot be used to prove a short-duration power figure.

The Table Ends Where It Ends

Three of the six TC tables stop at 60 minutes: the TC80 at 20.36 kW, the TC100 at 25.45 kW and the TC200D at 51 kW. None of them carries a 120-minute or 180-minute value, and the TC80 note states there is no 5-minute data either, so do not extrapolate. A two-hour requirement cannot be answered from a table that stops at one hour.

Only two tables reach beyond one hour. The TC100E is the only 512V table that covers 2, 3 and 5 hours, and the TC150E is the only 768V table that does. The TC150E reads 147 kW at 30 minutes, 73.5 kW at 60 minutes, 36.75 kW at 120 minutes, 24.6 kW at 180 minutes and 14.7 kW at 300 minutes. A value between two listed rows, or beyond the last row, does not exist in the datasheet. It has to be confirmed by the manufacturer, not filled in by drawing a line between two points.

Same Energy, Different Power

The tables also show that stored energy and delivered power are not the same thing. The TC100E and the TC200D are both 512V 100Ah cabinets with 51.2 kWh of nominal energy, but their tables are far apart: at 15 minutes the TC200D delivers 200 kW while the TC100E has no 15-minute row at all and a maximum output of 98 kW. At 30 and 60 minutes they come close, 100 against 98 kW and 51 against 49 kW. The two cabinets only look alike in the middle of the table.

The same pattern appears between the 50Ah and 100Ah cabinets: the 50Ah TC100 lists 114 kW against the 100Ah TC100E at 98 kW. More stored energy does not mean more power.

What the Table Cannot Promise

A discharge table is a set of datasheet reference values, not a runtime promise for a specific project. The actual runtime depends on the real load, the UPS DC voltage window, the charging setup, the battery-room temperature and the condition of the cabinets. The table is the starting point for sizing; the project design and the manufacturer's confirmation are what turn a table row into a system that holds a load for the required time.

When reading a table, check four things: the runtime column matches the requirement, the power is read at that runtime and not at the headline row, the table actually covers that runtime, and the cabinet in the table is the one being quoted. Read that way, the table gives a fair comparison.

Related Project Resources

ZYKEVO Project Support

ZYKEVO is a China-side UPS and battery supply partner for regional service companies. Support may include requirement collection, high-voltage lithium battery direction review, battery cabinet and BMS coordination, OEM presentation, documentation and shipment coordination for suitable projects.

For high-voltage lithium battery matching, share the exact UPS model, DC voltage window, charging information, measured load, required runtime, BMS requirements and site conditions with ZYKEVO.

Have a UPS or battery project?

Leave your name, phone or WhatsApp, email, country and a short message. We will review it and get back to you.