Most high-voltage lithium batteries for UPS projects sit at 192V, 384V or 512V. A 768V battery raises the DC bus higher still, and two cabinet types carry that voltage: a 50Ah high-rate cabinet and a 100Ah energy-type cabinet. They share a nominal voltage and a voltage window but serve different duties, and a 768V battery is assessed against the exact UPS model rather than treated as a standard platform direction.
Two Cabinets, One Voltage, Different Jobs
The 50Ah cabinet holds 38.4kWh, with a maximum output power of 171kW and a standard discharge of 150kW at 15 minutes. The 100Ah cabinet holds 76.8kWh, with a maximum output power of 147kW and a standard discharge of 147kW at 30 minutes.
The larger cabinet delivers less peak power than the smaller one. The same relationship appears at 512V, where the 50Ah cabinet reaches a higher maximum output than the 100Ah cabinet. Capacity in kWh and power in kW describe different things: a bigger energy store does not automatically mean bigger power output.
Reading the Two Discharge Tables
Each cabinet has a constant-power discharge table covering only its own range.
The 50Ah cabinet table runs from 10 to 60 minutes: 171kW at 10 minutes, 150kW at 15 minutes, 75.6kW at 30 minutes, 50.7kW at 45 minutes and 38.17kW at 60 minutes. It has no 120, 180 or 300 minute data, so it cannot support a longer runtime.
The 100Ah cabinet table runs from 30 to 300 minutes: 147kW at 30 minutes, 73.5kW at 60 minutes, 36.75kW at 120 minutes, 24.6kW at 180 minutes and 14.7kW at 300 minutes. It is the only 768V table covering two, three and five hours, but it starts at 30 minutes, so it has no 10 or 15 minute data and cannot support short-duration power.
The two tables answer different questions: how much power for how many minutes, or how many minutes at a lower load.
The Voltage Window the UPS Must Accept
Both cabinets share one voltage window: charging at 816 to 828V with a cut-off at 864V, rated discharge cut-off at 672V and minimum discharge cut-off at 636V. The UPS DC range, its low-voltage shutdown point and its charger must fit inside this window. A UPS that cannot charge to 816V or accept a 636V minimum will not work with either cabinet.
Charging current also differs: the 50Ah cabinet charges at a rated 25A and a maximum 50A, the 100Ah cabinet at a rated 50A and a maximum 100A. Recharge time depends on that current as well as on the UPS charger. Short-circuit current is about 4000A for the 50Ah cabinet and about 4500A for the 100Ah cabinet.
The datasheet notes compatibility with two-wire and three-wire systems. Its parameter table lists no CAN, RS485 or TCP/IP entries, so interfaces are confirmed separately: the CAN and RS485 protocol documents apply to all TC series models and can be reviewed against the UPS side.
Size, Weight and Cabinet Layout
The two cabinets also differ physically: the 50Ah cabinet weighs about 780kg and measures 1000 by 600 by 2300mm, while the 100Ah cabinet weighs about 940kg and measures 1000 by 1150 by 1500mm. Its 1150mm depth differs from the 600mm depth of the other models, so floor space and service clearance need a separate check.
Inside, the cabinets use different modules: 51.2V 50Ah in the 50Ah cabinet and 51.2V 100Ah in the 100Ah cabinet. Variants marked with (S) carry the system BMS for multi-cabinet parallel setups; the standard rack carries a single-cabinet BMS. Both are rated IP21, with self-discharge of no more than 2% per month.
What to Confirm Before Specifying 768V
A 768V direction starts with the same review as any high-voltage battery, with a few extra checks:
- The exact UPS brand and model, and its full DC operating window against 816 to 828V charging and a 636V minimum
- Whether the duty is short and high-power or longer and lower-power, and which discharge table covers it
- Charging voltage and current the UPS can actually supply
- Communication and protection interfaces, confirmed against the protocol documents rather than assumed from the datasheet
- Floor loading, footprint and access for a cabinet up to about 940kg and 1150mm deep
- The site temperature range, since available capacity changes with temperature
A 768V battery does not replace a 512V battery. It is a higher-voltage direction for UPS models whose DC bus and charger can accept it. Confirm the UPS window first, then read the table that matches the duty: power or runtime.
Related Project Resources
- Learn how 192V, 384V and 512V lithium battery systems compare.
- Check the DC bus voltage checklist for lithium battery projects.
- Compare high-rate versus extended-runtime batteries.
- Read why UPS power alone cannot size a battery.
- Review the RS485 and CAN BMS communication checklist.
- Send Your Requirement for a 768V compatibility review.
ZYKEVO Project Support
ZYKEVO is a China-side UPS and battery supply partner for regional service companies. Support may include requirement collection, high-voltage lithium battery direction review, battery cabinet and BMS coordination, OEM presentation, documentation and shipment coordination for suitable projects.
For high-voltage lithium battery matching, share the exact UPS model, DC voltage window, charging information, measured load, required runtime, BMS requirements and site conditions with ZYKEVO.