Connecting a high-voltage lithium battery to a UPS starts with communication. Two protocol documents define how the battery BMS talks to the outside world — CAN Protocol V1.1 and RS485 Protocol V1.2 (Modbus RTU). Both apply to all TC series models, and both can be shared with customers and UPS-side engineers for integration review.
The documents define the BMS side only. Before a battery is connected, the settings, addresses and data points on both sides must match — the checklist below lists the questions to confirm with the UPS side.
First Confirm: One Cabinet or a Parallel System?
The battery BMS comes in two forms: RBMS, the battery management system of a single cabinet, and SBMS, the system BMS for a multi-cabinet parallel system. A cabinet marked Rack TCxxx carries RBMS only; TCxxx(S) carries SBMS.
Both documents mark each frame and register for RBMS, SBMS or both, so confirm the form first: the applicable frames, registers and addresses follow from that answer.
RS485 (Modbus RTU): The Settings to Match
On RS485, the BMS is the slave and the external device — UPS, PCS or data acquisition equipment — is the master that starts communication.
Confirm these settings with the UPS side:
- Baud rate and format: default 9600 bps, 8 data bits, 1 stop bit, no parity; the baud rate can be changed through the host or HMI.
- Byte order: big endian — the opposite of CAN.
- Slave address: address 0x30 reads SBMS data. Addresses 1, 2, 3 and so on read the data of cabinet 1, cabinet 2, cabinet 3 and so on.
- Registers: SBMS running status uses registers 1000–1028. RBMS single-cabinet running status uses registers 1100–111F, covering warning events, primary and secondary protection events and the BMS self-test status. Battery data registers, configuration registers 0x4000–0x4003 and product information registers 0x4010–0x4033 — including a product serial number read — complete the map.
Ask the UPS side which registers it reads — the SBMS address, the cabinet addresses, or both.
CAN 2.0B: The Settings to Match
On CAN, the BMS sends its frames on a fixed cycle. Confirm these settings with the UPS side:
- Bus and rate: CAN 2.0B, default 125 kbps, configurable. Only extended frames are used.
- Byte order: little endian — the opposite of RS485.
- Send cycle: all frames go out every 1000 ms while the system runs without abnormality; alarm and protection frames go out immediately when their state changes.
- Frames: 0x351 carries charge and discharge current and voltage limits; 0x355 carries state of charge and state of health; 0x356 and 0x35E carry voltage and current, without and with a center tap; 0x35A carries warning and protection status; 0x35B carries charge and discharge enable; 0x35C carries power and energy; 0x35D carries remaining discharge time. 0x3C0 covers online cabinet count, dry-contact status and system status; 0x3D6 covers system configuration; 0x3D7 covers firmware and hardware versions. Per-cabinet battery data uses frames 0x400–0x9DB.
- Dry contacts: 4 dry-contact outputs, reported in frame 0x3C0.
Ask the UPS side which frame IDs it listens to, and how it uses remaining discharge time, warnings, protection frames and dry contacts.
What These Documents Do Not Answer
The two protocol documents define the BMS side only. They name no UPS brand, and they do not prove compatibility with any specific UPS model. The UPS side must provide its own official protocol, with the same settings and data definitions, for the pairing to be reviewed.
TCP/IP is also outside these documents: no TCP/IP protocol document exists, and the RS485 register map carries only an Ethernet self-test status bit, so TCP/IP is not a confirmed interface for the battery BMS.
Both documents are 2023 versions — CAN V1.1 dated 2023-4-3, RS485 V1.2 dated 2023-6-9 — check for a newer version before starting an integration review.
Pre-Connection Checklist
Before the battery is connected to the UPS, confirm:
- Single cabinet (RBMS) or multi-cabinet parallel system (SBMS)?
- RS485 or CAN — or dry contacts only?
- RS485: baud rate, big endian byte order, slave addresses, and the registers the UPS reads.
- CAN: 125 kbps rate, extended frames, little endian byte order, and the frame IDs the UPS listens to.
- Which data points the UPS uses: state of charge and health, remaining discharge time, warnings, protection events, dry contacts.
- The UPS-side official protocol document for the exact UPS model.
- Whether TCP/IP is required — no protocol document exists for it.
- The latest version of each protocol document.
Related Project Resources
- Follow the CAN and RS485 compatibility guide for the protocol, data-point and control-logic review before approval.
- Follow the UPS DC bus voltage checklist to collect the UPS DC bus evidence before selecting a battery.
- Follow the UPS lithium battery selection guide for the complete DC, load, charging, topology and site review.
- Review the high-voltage lithium battery for UPS product direction.
- Send Your Requirement for a communication and compatibility review.