A battery cabinet is more than stored energy: its battery management system watches the cells and reports what it sees. Two protocol documents describe that reporting for the TC family — CAN V1.1 (file GCE016, 2023-04-03) and RS485 V1.2 (file GCE015, Modbus RTU, 2023-06-09). Both apply to all six TC models, and both may be shared with a UPS-side engineer doing the integration. This article lists the data the BMS sends — not a claim that any specific UPS accepts it.
The Headline Numbers: SOC, SOH and Remaining Time
The most useful CAN frames carry the figures an operator asks for first. Frame 0x355 carries state of charge (SOC) and state of health (SOH); 0x35D carries remaining discharge time; 0x35C carries power and energy; 0x356 and 0x35E carry voltage and current — 0x356 without a neutral line, 0x35E where a neutral or centre tap is used. Frames 0x351 and 0x35B carry the charge and discharge current and voltage limits and the charge and discharge enable.
Together these frames answer the operating questions — charge level, estimated remaining life, discharge time left at the present load, and what charge and discharge the BMS allows. The RS485 and CAN checklist article covers what to confirm before connecting; this article covers what flows once the link is running.
Cell-Level Detail: Voltages and Temperatures
Below the cabinet totals, the BMS reports the extremes across the cells: frames 0x358 and 0x359 carry the highest and lowest single-cell voltage and temperature for a single cabinet, with further ranges in detail — 0x360–0x36E for cell voltages, 0x380–0x38E for temperatures. These extremes show a weak cell or a hot spot that the cabinet totals would hide.
The CAN link sends all frames once every 1000ms while there is no fault; on an alarm or protection change, the alarm frame is sent at once. The link is CAN 2.0B at 125 kbps by default, configurable, extended frames only, little-endian byte order.
Alarms and Protection Status
Frame 0x35A carries the alarm and protection status for a single cabinet (RBMS). In a multi-cabinet system, frames 0x3C1–0x3CF carry the alarm and protection status of each cabinet, and frame 0x3D0 carries the same for the system-level BMS (SBMS). The documents define the reporting path, not the protection settings of any specific installation.
Over RS485, the same information appears as event tables in the running-status registers — alarm, first-level protection, BMS self-check and second-level protection — inside the RBMS range 1100–111F; SBMS running status sits in registers 1000–1028.
Multi-Cabinet Reporting: What Only the SBMS Sends
A single cabinet is managed by its RBMS; a multi-cabinet parallel system adds an SBMS, the system-level BMS, and several frames exist only for that case. Frame 0x3C0 carries the number of online battery cabinets, the dry-contact states and the system status. Frames 0x3A0–0x3AE carry each cabinet's current, 0x3D2–0x3D5 carry each RBMS contactor and breaker state, 0x3D6 carries the system configuration and 0x3D7 carries the system software and hardware versions. Frames 0x400–0x9DB carry each cabinet's battery data, again only with SBMS.
Four dry-contact outputs are part of the same reporting: bits 0–3 of frame 0x3C0 carry the output states of dry contacts 1–4.
The Same Data Over RS485 Modbus RTU
The RS485 document describes a Modbus RTU link: 9600 bps, 8 data bits, 1 stop bit, no parity by default, baud rate changeable through the host computer or HMI. Byte order is big-endian — the opposite of CAN. The BMS is the slave; the external device, such as the UPS or a data logger, is the master and starts the communication.
Addressing is by cabinet: slave address 0x30 reads SBMS data, and addresses 1, 2, 3 and so on read cabinet 1, 2, 3 in turn. Configuration registers sit at 0x4000–0x4003, and product information registers at 0x4010–0x4033 include reading the product serial number. Version 1.2 added charge/discharge enable and power information to the RBMS running status; version 1.1 had added online cabinet data, dry-contact status, voltage/temperature extremes, chargeable and dischargeable cabinet counts, configuration registers and serial number reading.
What the Documents Do Not Cover
Three limits belong with the data list. First, neither document names any UPS brand: the protocol describes the battery side only, so it does not prove compatibility with a specific UPS model, and the UPS side still needs its own official protocol document; the CAN and RS485 compatibility guide sets out that check. Second, there is no TCP/IP protocol document — the two documents cover RS485 and CAN only, with a single Ethernet self-check bit in the RS485 document. Third, the CAN maintenance frame 0x357 is marked as not supported yet, and both documents are 2023 versions, so a newer version, if one exists, takes precedence.
Related Project Resources
- Read the RS485 and CAN checklist article for what to confirm before connecting.
- Read the CAN and RS485 compatibility guide for the protocol-matching record.
- Review the high-voltage lithium battery for UPS product direction.