A high-voltage lithium battery datasheet lists three temperature ranges, not one: storage from -5 to 35°C, discharge from -20 to 65°C, and charging from 0 to 45°C. The same three ranges appear in every TC series datasheet, from the 409.6V cabinet to the 768V cabinets. Each range answers a different question — where the cabinet can wait, where it can deliver power, and where it can accept charge — and mixing them up is how a battery room gets specified wrong.
Three Ranges, Three Questions
The storage range is the narrowest: -5 to 35°C. It covers the room a cabinet waits in between delivery and commissioning, and the room it stands in while idle. A warehouse or battery room that drifts above 35°C in summer or below -5°C in winter sits outside the stated storage range, even if the battery would still discharge there.
The discharge range is the widest: -20 to 65°C. The battery can deliver power across it. But delivering power is not the same as delivering full capacity, and the discharge range says nothing about how much capacity is available at the cold end. That question belongs to the temperature-capacity curve, covered below.
The charging range starts at 0°C and runs to 45°C. Charging below 0°C sits outside the stated range. A battery room that drops below freezing in winter needs a heating or placement review before the battery is specified, not after it is installed and the charger first runs on a cold morning.
Capacity Falls as Temperature Falls
The datasheet includes a temperature-capacity curve at a 1C rate. It uses 25°C as the 100% reference, and it reads about 65% at -20°C. That reading comes from the curve itself: the datasheet gives no numeric table of capacity against temperature, so the curve shows direction rather than a precise figure. Do not use it as a derating table.
The practical point is simple. A cold battery room delivers less usable capacity per discharge than the same battery at 25°C, which changes runtime expectations. Check the constant-power discharge tables against the actual battery-room temperature, not only against the 25°C reference. Follow the guide to reading a constant-power discharge table for how the table rows work, and the capacity calculation guide for how load and runtime turn into a configuration.
Storage Between Delivery and Commissioning
A battery does not stop ageing when it is switched off. The datasheet lists self-discharge at no more than 2% per month, and its cautions say to store the battery at 50% capacity and top it up every six months. At the listed maximum rate, six months without a top-up removes up to about 12% of charge — and that is before the battery has delivered a single minute of backup.
The storage rule matters most when the schedule slips. A cabinet can arrive months before the UPS is ready, or sit in a warehouse while the site is prepared. Somebody has to own the top-up: who checks the charge, and when. A cabinet that arrives at 50% and is never topped up reaches commissioning with less charge than the project assumed, and the shortfall is discovered at the worst possible moment — during the first runtime check.
Storage temperature and storage charge belong in the same plan. The cabinet waits inside -5 to 35°C, at 50% capacity, with a top-up every six months.
The Room and the Cabinet
The cabinets carry an IP21 protection rating, so the battery room still needs to be a dry indoor space with the cabinet protected from water and dust beyond that rating. The datasheet cautions add the handling rules: no short circuit, no crushing, no disassembly, no heating, no immersion in water.
Two cautions deserve attention during installation and service. First, a cabinet can hold more than one DC source, so disconnect all DC power before opening it — not just the main breaker. Second, wait five minutes after disconnecting before opening the cabinet, and do not touch exposed terminals.
Questions to Settle Before Specifying
Before a battery is specified for a site, settle the temperature and storage questions in writing:
- What is the coldest battery-room temperature in winter, and the hottest in summer?
- Does the room ever fall below 0°C, where charging sits outside the stated range?
- How long will the cabinet wait between delivery and commissioning, and who tops it up?
- Was the runtime calculated at 25°C, or at the actual room temperature?
- What heating, ventilation or placement change is needed if the room fails any of the three ranges?
Temperature is not a footnote to a lithium battery project. It decides how much capacity the battery delivers, whether it can charge on a cold morning, and what condition it is in when commissioning starts. The datasheet gives the ranges and the storage rules; the project has to supply the room that meets them.
Related Project Resources
- Read the cycle-life and design-life figures with their conditions attached before comparing lifetime numbers.
- Check the 512V lithium battery platform and the high-voltage lithium battery hub for the platforms these ranges apply to.