Dry Contacts on a Lithium Battery Cabinet: The Simple Signals a UPS Reads

Beyond the data frames, a lithium battery cabinet speaks in dry contacts: four outputs and four inputs, each one bit, closed or open. The RS485 protocol names three of the outputs — charger off, system abnormal, BCB trip — and one input that opens every breaker at once.

A battery cabinet talks to the UPS in two languages at once. The data frames carry numbers: voltage, current, state of charge, remaining time. The dry contacts carry one bit each: closed or open — a plain relay contact with no voltage or data of its own, readable without decoding a protocol. This article follows CAN V1.1 and RS485 V1.2, which apply to all TC series models.

The Four Outputs: What the Cabinet Says

RS485 protocol V1.2 carries the dry-contact status in SBMS register 1025. Bits 0 to 3 are the four outputs, with 1 meaning valid (closed) and 0 meaning invalid (open), and the document names three of them: output 1, the signal that the charger needs to turn off; output 2, the lithium battery system abnormal signal; output 3, the BCB (battery circuit breaker) trip signal. Output 4 has a bit and a state, but no meaning in the document.

CAN protocol V1.1 carries the same four output states in frame 0x3C0, byte 3, bits 0 to 3, with 1 meaning valid (closed) and 0 meaning invalid (disconnected) — but names no meaning for any of them. The two documents agree on the states and differ on the meanings: the three output meanings live in the RS485 document only.

A closed output is a signal, not a measurement: it says the system is abnormal, not which cell or temperature is out of range.

The Four Inputs: What the Cabinet Hears

The cabinet also accepts four dry-contact inputs. In the RS485 document they sit in register 1025, bits 8 to 11, with 1 meaning valid and 0 meaning invalid. The document states one meaning: when the SBMS detects the input 1 signal, it issues a command to notify each battery cabinet to open its circuit breaker immediately. Inputs 2 to 4 have bits and states but no meaning, and bits 4 to 7 of the register are reserved.

On the CAN side the four inputs sit in the same byte, bits 4 to 7, with 1 meaning valid and 0 meaning invalid. The positions do not match the RS485 layout, where the inputs sit at bits 8 to 11 and bits 4 to 7 are reserved. An integration reading both protocols has to keep the two layouts apart instead of assuming one maps onto the other.

Input 1 is the sharp end of the feature: one external signal opens every breaker at once, so its wiring and source are integration decisions, not something to improvise on site.

One Frame Carries the Whole System State

Dry-contact status is reported at the system level, not per cabinet: CAN frame 0x3C0 is marked SBMS only, and RS485 register 1025 sits in the SBMS running-status range 1000 to 1028 — the SBMS/RBMS split the parallel cabinets article explains.

The same CAN frame 0x3C0 packs the rest of the system picture around the contacts. Byte 0 is the number of online cabinets, using the online definition from the self-test article: self-test passed and at least one contactor closed. Bytes 1 to 2 carry the highest cell voltage in millivolts. Byte 4 is the system status: 0x00 normal, 0x01 Warning (prompt only), 0x02 Alarm (level 1 protection, contactor disconnected), 0x03 Fault (level 2 protection, circuit breaker open). One frame therefore gives the online count, the worst cell, the system state and the dry contacts together, sent every 1000ms while there is no fault and at once when an alarm or protection state changes.

What the Documents Do Not Say

The protocol documents define the signals and their states. They do not give contact ratings, terminal assignments or wiring details, and they leave output 4 and inputs 2 to 4 unnamed. Those gaps are closed at integration, with the supplier, before commissioning — not by guessing on site.

The two protocol documents carry no UPS brand names anywhere in their text; whether the UPS acts on a closing contact depends on the UPS model and its own documentation, and the compatibility guide lists the checks that settle that question.

What to Check at Commissioning

Three reads settle the dry-contact check. First, read the states — CAN frame 0x3C0 byte 3, or RS485 register 1025 — and confirm each bit reads as expected at rest. Second, confirm which input layout is in use, since the two protocols place the inputs differently. Third, test input 1 only as a planned shutdown test with the supplier's procedure: it opens every breaker at once.

Related Project Resources

ZYKEVO Project Support

ZYKEVO is a China-side UPS and battery supply partner for regional service companies. Support may include requirement collection, high-voltage lithium battery direction review, battery cabinet and BMS coordination, OEM presentation, documentation and shipment coordination for suitable projects.

For high-voltage lithium battery matching, share the exact UPS model, DC voltage window, charging information, measured load, required runtime, BMS requirements and site conditions with ZYKEVO.

Have a UPS or battery project?

Leave your name, phone or WhatsApp, email, country and a short message. We will review it and get back to you.