A battery management system does more than report state of charge. When a value crosses a line, it acts: a warning only prompts, a level 1 protection opens the contactor, and a level 2 protection opens the circuit breaker. The TC battery family's RS485 and CAN protocols define all three levels.
Three Levels, Three Different Outcomes
The CAN protocol carries the system status as a single byte in frame 0x3C0: normal (0x00), Warning (0x01, prompt only), Alarm (0x02, level 1 protection, contactor disconnected) and Fault (0x03, level 2 protection, circuit breaker open). RS485 reports the same three levels in separate alarm, primary and secondary protection registers.
At Warning, the battery stays connected and keeps working while the event is flagged. At Alarm, the contactor opens and the cabinet stops. At Fault, the circuit breaker opens as well. So ask first which level it is.
The Fifteen Conditions the BMS Watches
The protocol lists the same conditions at all three levels, each with its own threshold in the BMS configuration. Fifteen conditions are monitored: voltage (total voltage high and low, cell voltage high and low), current (charge overcurrent, discharge overcurrent), temperature (charge high and low, discharge high and low, imbalance inside the string), plus low state of charge, low insulation resistance, cell imbalance and BMU communication failure. Secondary protection adds one more: external protection, where the breaker is disconnected by hand or opened by a short circuit outside the battery.
The protocol defines the events and their bit positions; the threshold numbers are BMS configuration values, not published in the protocol document. So read a trip by event name and level: a cell overvoltage warning and a level 1 protection are the same condition at two lines, and the second has already opened the contactor.
What the UPS Sees When a Trip Happens
On CAN, the BMS sends the RBMS warning and protection frame 0x35A, the per-cabinet frames 0x3C1 to 0x3CF, and the SBMS frame 0x3D0. All frames are sent every 1000 ms when nothing is wrong, and the alarm frame is sent at once when the state changes. Frames 0x3D2 to 0x3D5 report the contactor and breaker state of every cabinet, so the UPS side can see whether a cabinet is back in the circuit.
On RS485 the BMS is the slave and the UPS is the master, reading the running status registers — 1000 to 1028 for the system BMS, 1100 to 111F for each cabinet — where each of the three levels has its own register. Four dry-contact outputs are also available, reported in frame 0x3C0, with 1 meaning closed and 0 meaning open; which signal each contact carries is set in the project wiring, so confirm the assignment first.
A cabinet counts as online only when its self-test passes and a main or discharge contactor is closed. The self-test covers the Hall sensor, Ethernet, memory chip and BMU supply voltage, with 1 meaning passed and 0 failed. A cabinet that fails its self-test never reports online, even if its voltage looks normal.
Limits and Enable Signals
Before protection comes the limit the UPS should work inside. On CAN, frame 0x351 carries the charge and discharge current and voltage limits, and frame 0x35B the enable state. On RS485, registers 1122 and 1123 report the current maximum charge and discharge power, and 1120 and 1121 accept the enable commands: 0xAAAA to allow, 0x5555 to stop. A UPS that reads these limits can stay inside them instead of waiting for the BMS to trip.
Short-Circuit Currents and the Breaker
The datasheets give a short-circuit current for each cabinet: about 4000 A for the TC80, TC100 and TC150, about 4500 A for the TC100E and TC150E, and about 9000 A for the TC200D. Those figures are the fault current the cabinet can deliver into a short circuit, which is why the breaker is the last line of protection and why the cautions say never to short-circuit the battery. The same cautions say to disconnect all DC power and wait five minutes before opening a cabinet.
What to Confirm in a Project
Check three things in a project: which protocol the UPS reads and which frame or register it monitors; the dry-contact assignment, if the UPS relies on a contact; and the recovery steps after a trip. The protocol reports the contactor and breaker states but does not state whether a contactor recloses on its own or needs a reset, so confirm the recovery procedure with the supplier before the first trip, not after.
Related Project Resources
- Read the RS485 and CAN BMS communication checklist.
- Read what a lithium battery BMS reports to the UPS.
- Read how to handle a lithium battery cabinet.
- Read parallel lithium battery cabinets and SBMS.
- Read the CAN and RS485 compatibility guide.
- Review the high-voltage lithium battery for UPS product direction.
- Send Your Requirement for a BMS review against the actual UPS model.