Charging a High-Voltage Lithium Battery: Charge Voltage and Current Explained

A 512V cabinet charges at 544 to 552V and stops at 576V; a 768V cabinet charges at 816 to 828V and stops at 864V. The charging figures on the datasheet are the numbers the UPS charger has to respect, and the rated current and the maximum current are two different limits.

A high-voltage lithium battery datasheet lists four charging figures: a rated charge current, a maximum charge current, a rated charge voltage, and a charge cut-off voltage. A fifth figure, the equalization voltage, sits alongside them. These five numbers describe the charger the battery expects. The UPS rectifier or charger has to work inside them, and a charger set outside them is outside the datasheet — whatever the UPS is rated for.

The Charging Figures Across the Six Models

The six TC series cabinets fall into three voltage platforms, and the charging figures follow the platform:

  • 409.6V — TC80 (50Ah, 20.48kWh): rated charge current 25A, maximum 50A, rated charge voltage 435.2 to 441.6V, charge cut-off 460.8V, equalization voltage above 435.2V.
  • 512V — TC100 (50Ah, 25.6kWh): 25A rated, 50A maximum, 544 to 552V, cut-off 576V, equalization above 544V.
  • 512V — TC100E and TC200D (100Ah, 51.2kWh): 50A rated, 100A maximum, 544 to 552V, cut-off 576V, equalization above 544V.
  • 768V — TC150 (50Ah, 38.4kWh): 25A rated, 50A maximum, 816 to 828V, cut-off 864V, equalization above 816V.
  • 768V — TC150E (100Ah, 76.8kWh): 50A rated, 100A maximum, 816 to 828V, cut-off 864V, equalization above 826V.

Two patterns are worth noting. First, the charge voltage sits above the nominal voltage on every platform: a 512V battery charges at 544 to 552V, and a 768V battery charges at 816 to 828V. The nominal voltage is the platform name, not the charging voltage. Second, the 100Ah cabinets charge at twice the current of the 50Ah cabinets on the same platform — 50A rated against 25A — while the voltage figures stay the same.

Rated Current and Maximum Current Are Two Limits

The rated charge current is the normal figure. The maximum charge current is the ceiling. On the TC100E and the TC200D, those two figures are 50A and 100A; on the TC100 and the TC80, they are 25A and 50A. A charger configured to the rated current works inside the datasheet. A charger configured above the maximum current does not, and the datasheet gives no figure beyond the maximum.

Dividing capacity by current gives a rough sense of scale. A 50Ah cabinet at a 25A rated current, or a 100Ah cabinet at a 50A rated current, divides out to about two hours from empty — if the current stayed constant. The datasheet gives no charge-time figure, so that division is arithmetic, not a measured charging time, and charging current falls as the battery nears full charge, so the real time is longer than the division suggests. Do not quote two hours as a charging time.

Cut-Off Voltage and the DC Window

The charge cut-off voltage is the top of the battery's DC window: 460.8V on the 409.6V cabinet, 576V on the 512V cabinets, 864V on the 768V cabinets. The charger stops there. The bottom of the window is the discharge cut-off voltage: 358.4V rated and 339.2V lowest on the 409.6V cabinet, 448V rated and 424V lowest on the 512V cabinets. The 768V TC150 lists a lowest DC voltage of 636V.

Put together, the window for a 512V cabinet runs from 424V at the lowest discharge cut-off to 576V at the charge cut-off. The UPS has to accept that whole window — its DC operating range, its minimum DC voltage and its low-battery cut-off all have to sit inside it. Follow the DC bus voltage checklist guide for the checks that confirm it.

What to Confirm Before the Charger Is Connected

Four questions settle the charging side of a project:

  • Is the charger voltage setpoint inside the rated charge voltage range for the platform — 544 to 552V on a 512V cabinet, not the 512V nominal figure?
  • Is the charger current limit at or below the maximum charge current — 50A on a 50Ah cabinet, 100A on a 100Ah cabinet?
  • Does the charger respect the charge cut-off voltage as a stop, and is the equalization voltage on record for the exact model?
  • Is the battery room inside the 0 to 45°C charging range? Charging below 0°C sits outside the stated range, as the battery-room temperature article explains.

Charging voltage and current are also on the list of information a supplier needs before quoting, covered in what information a supplier needs before quoting. The charger settings and the battery figures have to be agreed before the battery is ordered, not discovered at commissioning.