High-Voltage Lithium Battery Cabinet Weight and Footprint: Planning the Room

Six cabinets, three heights, two footprints and weights from about 420kg to about 940kg. A battery is specified by power and runtime, but it is delivered by weight and size — and the room has to be planned for both.

A high-voltage lithium battery is specified by power and runtime, but it is delivered by weight and size. The six TC series cabinets weigh from about 420kg to about 940kg, stand from 1500mm to 2300mm tall, and sit on two different footprints. None of that appears in a runtime calculation, and all of it decides whether the cabinet can reach the room, stand on the floor, and be serviced once it is there.

Weight and Size Across the Six Models

The datasheet figures, per model:

  • TC80 (409.6V, 50Ah, 20.48kWh): about 420kg, 1000 × 600 × 1500mm.
  • TC100 (512V, 50Ah, 25.6kWh): about 550kg, 1000 × 600 × 2000mm.
  • TC100E (512V, 100Ah, 51.2kWh): about 640kg, 1000 × 600 × 2000mm.
  • TC200D (512V, 100Ah, 51.2kWh): about 900kg, 1000 × 600 × 2000mm — or 2300mm tall when the fire-suppression module is fitted.
  • TC150 (768V, 50Ah, 38.4kWh): about 780kg, 1000 × 600 × 2300mm.
  • TC150E (768V, 100Ah, 76.8kWh): about 940kg, 1000 × 1150 × 1500mm.

The TC150E breaks the pattern: it is the heaviest cabinet and the shortest, and the only one that is 1150mm deep instead of 600mm. Cabinets in one family do not share one shape, so the dimensions have to be checked per model, not per platform.

Floor Loading: Weight Over Footprint

Floor loading is weight divided by footprint. Five cabinets sit on 1000 × 600mm, which is 0.6 square metres; the TC150E sits on 1000 × 1150mm, or 1.15 square metres. The arithmetic gives:

  • TC80: about 420kg over 0.6m² — about 700kg per square metre.
  • TC200D: about 900kg over 0.6m² — about 1,500kg per square metre.
  • TC150E: about 940kg over 1.15m² — about 820kg per square metre.

The heaviest cabinet does not put the heaviest load on the floor: the TC150E spreads its 940kg over nearly twice the footprint of the TC200D. Compare these figures with the floor's rated load, which comes from the building record — the battery datasheet gives the weight, not the floor rating.

Three 512V cabinets share one footprint and one height — TC100, TC100E and TC200D all measure 1000 × 600 × 2000mm — but weigh about 550kg, 640kg and 900kg. Swapping one model for another changes the floor load even when nothing about the room layout changes. The floor check has to be repeated for the exact model, not carried over from a similar one.

Height and the Delivery Route

The tallest cabinets stand 2300mm: the TC150, and the TC200D with its fire-suppression module. The shortest stand 1500mm: the TC80 and the TC150E. The route from the truck to the room has to clear the cabinet's height and depth — doors, corridors, lifts and turns — and the room itself has to take the height. The datasheet gives the cabinet dimensions; the route has to be measured on site.

The fire-suppression module deserves a line of its own. On the TC200D it adds 300mm of height, taking the cabinet from 2000mm to 2300mm. A room planned for the 2000mm figure is the wrong room for the cabinet as delivered. Confirm whether the module is fitted before the room and the route are planned.

What Else the Cabinet Needs in the Room

Weight and size are the start, not the whole plan. The cabinets carry an IP21 protection rating, so the room still has to be a dry indoor space, as the battery-room temperature article explains. A cabinet can hold more than one DC source, so disconnect all DC power and wait five minutes before opening it, and do not touch exposed terminals.

Cabling is part of the same check: five cabinets use M8 terminals and the TC200D uses M10. And when cabinets are paralleled for more power or longer runtime, the floor load multiplies with them — see parallel lithium battery cabinets for how multi-cabinet systems are put together.

Questions to Settle Before Delivery

  • What is the floor's rated load, and does the exact model's weight over its footprint sit inside it?
  • Does the delivery route clear the cabinet's height and depth — including the 2300mm height with the fire-suppression module, and the 1150mm depth of the TC150E?
  • Is the room height enough for the cabinet as delivered, not the cabinet as first quoted?
  • How much front and side access space does the layout leave? The datasheet lists cabinet dimensions only, so access space has to be settled in the room plan.
  • If the model changes late in the project, has the floor check been repeated for the new weight?

A battery that fits the electrical specification and not the room is a project that stops at the door. The datasheet gives the weight and the dimensions; the project has to supply the floor, the route and the room that take them.