409.6V High-Voltage Lithium Batteries for UPS: The Lower-Voltage Platform

The lowest-voltage cabinet in the TC range runs at 409.6V: 50Ah, 20.48kWh, 91.2kW at 10 minutes and 80kW at 15 minutes. It is the lightest cabinet in the range, and its DC window runs from 339.2V to 460.8V.

Most high-voltage lithium batteries for UPS projects sit at 192V, 384V or 512V, and the 768V cabinets sit at the top of the range. The 409.6V cabinet sits at the other end: the lowest-voltage cabinet in the TC range, a single model called the TC80, a short-duration, high-rate cabinet.

The Cabinet in Numbers

The TC80 is rated 409.6V, 50Ah and 20.48kWh, with a maximum output power of 91.2kW and a standard discharge of 80kW at 15 minutes. Inside, it uses TC10 modules rated 51.2V and 50Ah. The rack version, Rack TC80, carries a single-cabinet BMS; the TC80(S) version carries the system BMS for multi-cabinet parallel setups. It is the lightest cabinet in the six-model range at about 420kg, measuring 1000 by 600 by 1500mm. Its terminals are M8, and it is rated IP21.

Reading the Discharge Table

The TC80 discharge table covers five time points, from 10 to 60 minutes: 91.2kW at 10 minutes and 245A, 80kW at 15 minutes and 200A, 40.32kW at 30 minutes and 100A, 27kW at 45 minutes and 66.65A, and 20.36kW at 60 minutes and 50A.

Power falls by more than three quarters between the 10-minute row and the 60-minute row. The table has no 5-minute row and no 120-minute or 180-minute row, so it gives no figure for a 5-minute duty or for a two-hour duty. A runtime outside the table has to be confirmed with the manufacturer, not filled in by extending the line. The datasheet discharge curves on page 3 are marked at 0.2C, 0.5C, 1.0C and 4.0C; no TC datasheet gives any model a rated C-rate or a 6C figure.

The Voltage Window the UPS Must Accept

Charging runs at 435.2 to 441.6V, with a charge cut-off at 460.8V and an equalization voltage above 435.2V. The rated discharge cut-off is 358.4V and the minimum is 339.2V. The DC window therefore runs from 339.2V at the bottom to 460.8V at the top, and the UPS DC operating range, its low-battery cut-off and its charger must all sit inside it.

Charging current is 25A rated and 50A maximum, the same figures as the other 50Ah cabinets, and short-circuit current is about 4000A. The datasheet notes compatibility with two-wire and three-wire systems. Its parameter table lists no CAN, RS485 or TCP/IP entries, so interfaces are confirmed separately: the CAN and RS485 protocol documents apply to all TC series models and can be reviewed against the UPS side.

Same Capacity, Different Voltage Platform

The 409.6V cabinet is best read next to the 512V 50Ah cabinet, the TC100, because the two share a capacity and differ only in voltage. The TC100 holds 25.6kWh and delivers 114kW at 10 minutes, 100kW at 15 minutes, 50.4kW at 30 minutes and 25.45kW at 60 minutes. At every row it delivers more power, and it charges at 544 to 552V with a cut-off at 576V and a rated discharge cut-off of 448V.

The 768V 50Ah cabinet, the TC150, shows the same pattern one step further up: 38.4kWh, 171kW at 10 minutes and 150kW at 15 minutes. Capacity in Ah or kWh does not set the power figure; the voltage platform and the discharge table decide it.

Lifetime and Storage Figures

The TC80 lists a cycle life of 4000 cycles at 1C and 80% depth of discharge, and a 20-year design life. Its temperature ranges match the other models: storage from -5°C to 35°C, discharge from -20°C to 65°C, and charging from 0°C to 45°C. Self-discharge is no more than 2% per month, and storage follows the same rule as the other cabinets — 50% capacity, recharged every 6 months — covered in the battery-room temperature and storage article. The datasheet names UN38.3 and IEC62619 (cell) certifications, with no report numbers, scope or validity dates given.

What to Confirm Before Specifying 409.6V

  • The exact UPS model, and its full DC operating window against a 339.2V minimum and a 460.8V charge cut-off
  • Whether the duty sits inside the 10 to 60 minute table, and which row matches the required runtime
  • Charging voltage and current the UPS can supply: 435.2 to 441.6V at 25A rated
  • Communication interfaces, confirmed against the protocol documents rather than assumed from the datasheet
  • Floor loading for about 420kg on a 0.6 square metre footprint — about 700kg per square metre by division, while the floor rating itself comes from the building record

A 409.6V battery is not a smaller 512V battery: it has its own window, table and charging figures. Confirm the UPS window first, then read the row that matches the duty.

Related Project Resources

ZYKEVO Project Support

ZYKEVO is a China-side UPS and battery supply partner for regional service companies. Support may include requirement collection, high-voltage lithium battery direction review, battery cabinet and BMS coordination, OEM presentation, documentation and shipment coordination for suitable projects.

For battery matching, share the exact UPS model, DC voltage window, charging information, measured load, required runtime, BMS requirements and site conditions with ZYKEVO.

Have a UPS or battery project?

Leave your name, phone or WhatsApp, email, country and a short message. We will review it and get back to you.