A datasheet gives fixed ratings. The BMS gives live limits, and the two are easy to confuse: a UPS charging against the datasheet rating while the BMS has withdrawn permission is working against the battery, not with it. This article follows CAN V1.1 and RS485 V1.2, which apply to all TC series models.
Allowed or Not: The Enable Signal
The simplest thing the BMS communicates is a yes or a no. On CAN, frame 0x35B carries it in two bytes: byte 0, charging allowed — 0x00 no charging, 0x01 charging allowed; byte 1, discharge allowed — 0x00 no discharge, 0x01 discharge allowed. The same frame carries a shutdown control in bytes 2 to 3, where 0xCCCC means stop and other values are invalid; bytes 4 to 7 are unnamed in the document.
On RS485 the same control sits in registers 1120 and 1121 — charging enable and discharging enable — each written as 0xAAAA to allow and 0x5555 to stop. The BMS is the slave and the external device is the master, and communication is initiated by the master; the default link is 9600 bps, 8 data bits, 1 stop bit, no parity. On the CAN side the frames go out every 1000ms while there is no fault, and an alarm or protection frame goes out at once on a state change.
The enable signal is a state, not a setting to argue with: when it reads "no charging", the battery is not accepting charge, whatever the charger is configured to deliver. The charging article covers the datasheet charge voltages and currents; the enable signal says whether charging is happening now.
How Much: The Voltage, Current and Power Limits
Beyond yes or no, the BMS states how much. CAN frame 0x351 carries four limits: the charge voltage limit in steps of 0.1 V, the battery pack rated charging voltage; the charge current limit in steps of 0.1 A, the maximum allowable charging current; the discharge current limit in steps of 0.1 A, the maximum allowable discharging current; and the discharge voltage limit in steps of 0.1 V, the minimum voltage the pack allows to discharge to.
CAN frame 0x35C carries the same idea in power: bytes 0 to 1 are the charging power in kW, the current maximum allowable charging power, and bytes 2 to 3 are the discharge power. The RS485 document carries the two power limits in registers 1122 and 1123, again in kW, again as the current maximum allowable charge and discharge power.
The word "current" does the work: these are the limits in force now, not the nameplate ratings. A battery at a high state of charge, a low temperature or a protection boundary reports lower limits than the same battery resting. The discharge table article shows how deliverable power changes with time and load on paper; the protocol limits show what the battery allows at this moment.
Live Limits Versus Fixed Ratings
The datasheet says what the cabinet is built to do: charge currents, cut-off voltages, the constant-power table. The protocol says what this battery, in this state, allows right now. A project that sizes a charger from the datasheet alone has the rating; a commissioning check that reads frames 0x351 and 0x35C, or registers 1120 to 1123, has the live answer.
When a limit is crossed, the protection system acts — the protection article covers its three levels and the fifteen conditions it watches — so the limits here are the numbers the UPS stays inside.
What the Documents Do Not Say
The documents define the signals and the values. They do not state what the UPS must do when the enable signal reads "no charging" or "no discharge" — that response is in the UPS documentation, and the documents carry no UPS brand names anywhere in their text. They give no procedure for the shutdown control beyond the value itself: 0xCCCC means stop, other values are invalid. How a site uses it is an integration decision, confirmed with the supplier before commissioning.
What to Check at Commissioning
Four reads settle the check. First, frame 0x35B or registers 1120 and 1121: confirm charging and discharging both read allowed before the first charge. Second, frame 0x351: confirm the charge voltage and current limits match the charger configuration. Third, frame 0x35C or registers 1122 and 1123: confirm the maximum charge and discharge power. Fourth, read them again under load — a limit that reads one way at rest can read another way once the battery is working.
Related Project Resources
- Read charging a high-voltage lithium battery: charge voltage and current.
- Read how to read a constant-power discharge table.
- Read when a lithium battery BMS trips a protection.
- Read what a lithium battery BMS checks before it goes online.
- Read RS485 and CAN BMS communication checklist.
- Read the CAN and RS485 compatibility guide.
- Review the high-voltage lithium battery for UPS product direction.
- Send Your Requirement for a BMS and commissioning review.
ZYKEVO Project Support
ZYKEVO is a China-side UPS and battery supply partner for regional service companies. Support may include requirement collection, high-voltage lithium battery direction review, battery cabinet and BMS coordination, OEM presentation, documentation and shipment coordination for suitable projects.
For high-voltage lithium battery matching, share the exact UPS model, DC voltage window, charging information, measured load, required runtime, BMS requirements and site conditions with ZYKEVO.