Six High-Voltage Lithium Battery Models Compared: Voltage, Energy and Discharge Power

Six TC battery cabinets, three voltage platforms, one comparison table. The numbers show why two cabinets with the same voltage and the same energy can deliver very different power — and why the discharge table at the exact runtime matters more than the Ah label.

Six battery cabinets, three voltage platforms: TC80 at 409.6V, TC100, TC100E and TC200D at 512V, TC150 and TC150E at 768V. All six use square lithium iron phosphate cells, and every figure below comes from the six datasheets — including the gaps, where a datasheet has no data.

The Six Models at a Glance

| Model | Nominal voltage | Capacity | Energy | Max output | Standard discharge | |---|---|---|---|---|---| | TC80 | 409.6V | 50Ah | 20.48kWh | 91.2kW | 80kW @ 15min | | TC100 | 512V | 50Ah | 25.6kWh | 114kW | 100kW @ 15min | | TC100E | 512V | 100Ah | 51.2kWh | 98kW | 98kW @ 30min | | TC200D | 512V | 100Ah | 51.2kWh | 228kW | 200kW @ 15min | | TC150 | 768V | 50Ah | 38.4kWh | 171kW | 150kW @ 15min | | TC150E | 768V | 100Ah | 76.8kWh | 147kW | 147kW @ 30min |

Charge voltages follow the same three platforms: 435.2–441.6V with a 460.8V cut-off for TC80, 544–552V with a 576V cut-off for the 512V models, and 816–828V with an 864V cut-off for the 768V models. Rated discharge cut-offs are 358.4V, 448V and 672V, with minimum cut-offs of 339.2V, 424V and 636V. The charging article covers those voltages in detail.

The Same Energy Does Not Mean the Same Power

Start with TC100E and TC200D: both 512V, 100Ah and 51.2kWh, with nearly the same 30-minute figures — 98kW and 100kW. But TC200D reaches 228kW maximum output and 200kW at 15 minutes, while TC100E reaches 98kW maximum and its table starts at 30 minutes. A project needing 150kW for 15 minutes is served by one TC200D cabinet and by no single TC100E cabinet; the energy label does not show that.

The 768V pair shows the same pattern from the other side: TC150 holds 38.4kWh and TC150E holds 76.8kWh, twice the energy, yet TC150 has the higher maximum output, 171kW against 147kW. TC150 is the short-time cabinet, with 150kW at 15 minutes; TC150E is the extended-runtime cabinet, with 147kW at 30 minutes and a table that runs to 300 minutes. The model name does not say which is which — the discharge table does.

Short-Time Tables and Long-Duration Tables

Four models have tables from 10 to 60 minutes: TC80 (91.2, 80, 40.32, 27, 20.36kW), TC100 (114, 100, 50.4, 33.8, 25.45kW), TC200D (228, 200, 100, 68, 51kW) and TC150 (171, 150, 75.6, 50.7, 38.17kW). None of the four has data beyond 60 minutes, so their tables say nothing about a two-hour runtime.

Only two models carry tables from 30 to 300 minutes: TC100E reads 98, 49, 24.5, 16.4 and 9.8kW, and TC150E reads 147, 73.5, 36.75, 24.6 and 14.7kW, at 30, 60, 120, 180 and 300 minutes. Those are the only two tables in the family that cover two hours and beyond; the constant-power discharge table article explains how to read them without extending past their last point.

What Is Identical on All Six

Unchanged across the family: cycle life 4000 cycles at 1C and 80% depth of discharge, design life 20 years, protection IP21, self-discharge no more than 2% per month, and the same temperature ranges — storage -5°C to 35°C, discharge -20°C to 65°C, charging 0°C to 45°C. The temperature and storage article covers those ranges.

Certification is named the same way on all six — UN38.3 and IEC62619 for the cell, with no report numbers given — and the transport marking is UN3480, Class 9.

Physical Differences: Weight, Size and Terminals

Weights run from about 420kg (TC80) to about 940kg (TC150E). TC80 measures 1000 × 600 × 1500mm, TC100, TC100E and TC200D 1000 × 600 × 2000mm, and TC150 1000 × 600 × 2300mm. Two sizes break the pattern: TC200D is also listed at 2300mm high with a fire module fitted, the only fire-module height variant in the family, and TC150E is 1000 × 1150 × 1500mm — 1150mm deep, nearly double the 600mm of the other five. The cabinet weight and footprint article covers the room planning.

Terminals are M8 on five models and M10 on TC200D alone. Short-circuit current is about 4000A for TC80, TC100 and TC150, about 4500A for TC100E and TC150E, and about 9000A for TC200D — the highest-power cabinet also carries the highest fault current.

How to Use This Comparison

Start with the voltage platform — the UPS DC bus decides which of the three groups applies. Then match the duty — short-time power or extended runtime — using the discharge table at the exact runtime the project needs. Then check weight, depth and terminals against the room and the DC cabling. Communication and the full DC voltage window are checked separately; the capacity calculation guide and the DC bus voltage checklist cover those steps.

Related Project Resources

ZYKEVO Project Support