How to Read a High-Voltage Lithium Battery Datasheet for a UPS Project

A high-voltage lithium battery datasheet is three pages long, and every figure on it answers a different question. Read in order, it tells you what the cabinet is, what charger it expects, how long it holds a load, and how it must be stored and handled. Read out of order, the same figures mislead.

A high-voltage lithium battery datasheet is three pages long, and every figure on it answers a different question. Read in order, it tells you what the cabinet is, what charger it expects, and how long it holds a load. Read out of order, they mislead: the headline power is the shortest table row, and the nominal voltage is not the charging voltage.

Start With the Identity: Voltage, Capacity, Energy

Every datasheet opens with three identity figures: nominal voltage, rated capacity and nominal energy. Across the six TC models they read: TC80 — 409.6V, 50Ah, 20.48kWh; TC100 — 512V, 50Ah, 25.6kWh; TC100E — 512V, 100Ah, 51.2kWh; TC200D — 512V, 100Ah, 51.2kWh; TC150 — 768V, 50Ah, 38.4kWh; TC150E — 768V, 100Ah, 76.8kWh. Nominal energy is nominal voltage times capacity, so it follows directly from the first two figures. The voltage is the platform — 409.6V, 512V or 768V — and the platform decides which UPS DC window the cabinet can work with. The six-model comparison sets the six side by side.

The TC100E and the TC200D share 512V, 100Ah and 51.2kWh, but their maximum output powers are 98kW and 228kW, and the 50Ah TC100 lists 114kW against the 100Ah TC100E at 98kW. More stored energy does not mean more power. Identity figures name the cabinet; they do not size it.

Performance Figures: The Charger the Battery Expects

The performance table lists the charging figures the charger must respect, plus maximum output power, standard discharge and discharge cut-off voltages.

The charge voltage sits above the nominal voltage on every platform: a 512V cabinet charges at 544 to 552V and stops at 576V, a 768V cabinet charges at 816 to 828V and stops at 864V, and the 409.6V cabinet charges at 435.2 to 441.6V and stops at 460.8V. The 100Ah cabinets charge at twice the current of the 50Ah cabinets on the same platform. The charging article covers them in full.

The discharge cut-off voltages set the bottom of the DC window: 358.4V rated and 339.2V lowest on the 409.6V cabinet, 448V and 424V on the 512V cabinets, 672V and 636V on the 768V cabinets. Together they give the full DC window the UPS must accept.

The Discharge Table: The Runtime Page

The discharge table answers the runtime question, and it is the page most often read at the wrong row: power falls steeply as the runtime grows. Four of the six tables stop at 60 minutes; only the TC100E and the TC150E reach 300 minutes, and the table gives only the listed time points. The discharge table article explains how to read it row by row.

General Data: Storage, Life, Size, Certifications

The general data section holds the figures for the battery room: storage from -5°C to 35°C, discharge from -20°C to 65°C, charging from 0°C to 45°C, the same on all six models. Cycle life is 4000 cycles at 1C and 80% depth of discharge, and design life is 20 years. The temperature and storage article and the cycle-life article cover both.

Weight runs from about 420kg on the TC80 to about 940kg on the TC150E; the cabinet weight and footprint article works through the room planning. Terminals are M8 except on the TC200D, which uses M10; self-discharge is no more than 2% per month.

Certifications appear as names only: UN38.3 and IEC62619 at cell level, with transport identification UN3480, Class 9. The datasheets give no report numbers, scope or validity status.

Structure, Interfaces and Cautions

The first page names the module inside the cabinet and the rack variants: a rack without SBMS carries only the single-cabinet RBMS, while a rack marked (S) carries the system-level SBMS. The parallel cabinets article explains the difference.

Communication is where the datasheet stops and the protocol documents take over. The parameter table has no CAN, RS485 or TCP/IP entries; the protocols are two separate documents, CAN V1.1 and RS485 V1.2, and TCP/IP has none. The RS485 and CAN checklist article lists the checks.

The third page carries 14 cautions, identical across all six models: the 50% storage charge, the six-month top-up, and disconnecting all DC power and waiting five minutes before opening a cabinet. The handling article works through all fourteen.

What the Datasheet Never States

Warranty, lead time and price are not datasheet lines at all. The five-year battery warranty is ZYKEVO's stated position, covered in the warranty article. Usable energy is not stated either, and no UPS brand name appears in the datasheets or the two protocol documents.

Read in order, the datasheet gives a fair picture. Anything beyond it belongs in the written project documents, not in the datasheet.

Related Project Resources

ZYKEVO Project Support

ZYKEVO is a China-side UPS and battery supply partner for regional service companies. Support may include requirement collection, high-voltage lithium battery direction review, battery cabinet and BMS coordination, OEM presentation, documentation and shipment coordination for suitable projects.

For high-voltage lithium battery matching, share the exact UPS model, DC voltage window, charging information, measured load, required runtime, BMS requirements and site conditions with ZYKEVO.

Have a UPS or battery project?

Leave your name, phone or WhatsApp, email, country and a short message. We will review it and get back to you.